Browse by author
Lookup NU author(s): Graham Pannell, Dr Dave Atkinson, Dr Bashar Zahawi
Full text for this publication is not currently held within this repository. Alternative links are provided below where available.
Grid-connected wind turbine doubly fed induction generators (DFIGs) are sensitive to dips in supply voltage, so-called "grid faults". Fault ride through systems must be designed to manage the large and potentially dangerous fault currents in both stator and rotor circuits. However, DFIG fault response has been only partially or summarily treated in contemporary literature. This paper presents a detailed analytical analysis of wind turbine DFIG grid-fault response. The physical behavior of the machine is presented through a description of the flux-linkage response and later developed with analytical solutions of the generalized DFIG machine equations operating under fault conditions showing that the frequencies of the decay components of current deviate from pure dc and rotor speed due to magnetic drag effects. The analysis is experimentally verified and evaluated using a 7.5-kW test facility.
Author(s): Pannell G, Atkinson DJ, Zahawi B
Publication type: Article
Publication status: Published
Journal: IEEE Transactions on Energy Conversion
Year: 2010
Volume: 25
Issue: 4
Pages: 1081-1091
Print publication date: 09/11/2010
ISSN (print): 0885-8969
ISSN (electronic): 1558-0059
Publisher: IEEE
URL: http://dx.doi.org/10.1109/TEC.2010.2049494
DOI: 10.1109/TEC.2010.2049494
Altmetrics provided by Altmetric