Toggle Main Menu Toggle Search

Open Access padlockePrints

Partial Non-Zero Fault Response of Grid-Connected DFIG

Lookup NU author(s): Graham Pannell, Dr Shady Gadoue, Dr Bashar Zahawi, Dr Dave Atkinson

Downloads

Full text for this publication is not currently held within this repository. Alternative links are provided below where available.


Abstract

© 2018 IEEE. This paper presents a detailed experimental study of wind turbine DFIG response to non-zero grid faults that may occur at a considerable distance from the generator. An analytical solution of the generalized DFIG machine equations operating under non-zero fault conditions is developed in which the fault response is separated into three components: a natural response that describes zero voltage behavior, a component describing the retained voltage behavior and the forced response corresponding to the applied rotor voltage via the rotor-side power converter. The DFIG system fault response is examined experimentally using a 7.5kW test facility detailing example of a 500ms, 15% fault.


Publication metadata

Author(s): Pannell G, Gadoue S, Zahawi B, Atkinson DJ

Publication type: Conference Proceedings (inc. Abstract)

Publication status: Published

Conference Name: 2018 XIII International Conference on Electrical Machines (ICEM)

Year of Conference: 2018

Pages: 1630-1635

Online publication date: 25/10/2018

Acceptance date: 02/04/2018

ISSN: 2381-4802

Publisher: IEEE

URL: https://doi.org/10.1109/ICELMACH.2018.8506930

DOI: 10.1109/ICELMACH.2018.8506930

Library holdings: Search Newcastle University Library for this item

ISBN: 9781538624777


Share