Browse by author
Lookup NU author(s): Elvedin Halimic, Professor Brian Agnew, Dr Sandy Anderson, Dr Ian Potts
Full text for this publication is not currently held within this repository. Alternative links are provided below where available.
This paper provides a comparison of the operating performance of three alternative refrigerants for use in a vapour compression refrigeration cycle. The refrigeration capacity and COP of R401A, R290 and R134A were compared with those of R12 when used in a propriety vapour compression refrigeration unit initially designed to operate with R12. The results indicate that the performance of R134a is very similar to that of R12 justifying the claim that it is a drop in replacement for R12 but of the refrigerants tested it gave the poorest performance. When viewed in terms of green house impact however R290 showed the best performance. © 2003 Elsevier Science Ltd. All rights reserved.
Author(s): Halimic E, Ross D, Agnew B, Anderson A, Potts I
Publication type: Article
Publication status: Published
Journal: Applied Thermal Engineering
Year: 2003
Volume: 23
Issue: 12
Pages: 1441-1451
ISSN (print): 1359-4311
ISSN (electronic): 1873-5606
Publisher: Pergamon
URL: http://dx.doi.org/10.1016/S1359-4311(03)00081-4
DOI: 10.1016/S1359-4311(03)00081-4